Lightning arrester for PVT1 and PVT2 solar power systems

PVT1 and PVT2 are the latest lightning cutting designs from ERICO, including many features and utilities for customers:Untitled

  •  PVT1 and PVT2 are compact but meet high protection requirements, and they can be mounted on 35mm DIN Rail. 
  • Fits all solar power systems (Solar Power System)
  • The protective clasp enhances anti-vibration and shock protection for Lightning Strike Modules
  • Working status indicator (green = OK/red = FAIL)
  • There is a connection port for remote monitoring
  • Complies with EN 50539-11 standard
  • UL 1449 4th Edition certified.

Applications of lightning arresters PVT1 and PVT2:

The equipment of the solar power system (Inverter, Charge Controller, DC box, ...) may already have built-in lightning cutting components, but the lightning current of these available lightning cutting components is slightly lower, so it does not guarantee the protection against lightning transmission for the system. Therefore, it is advisable to increase and equip more lightning protection devices with higher protection to increase safety during system operation.

The PVT1 and PVT2 surge arresters are installed at the DC junction boxes (DC Joint Box) or at the DC inputs of the DC/AC inverters (DC/AC Inverter) of the solar power system.

Lines of lightning arresters for solar power systems

  • PVT1 PHOTOVOLTAIC SURGE PROTECTION CLASS I+II

The PVT1 lightning arrester provides the solution lightning protection reliable and efficient response lightning protection standards EN 50539-11 Type 1, Type 2 và UL® 1449 Edition 4 Type 1CA and have been certified by independent testing bodies The PVT1 product line features a wide range of safety and performance features for the harshest environments and a wide range of applications in industrial applications. The surge protection system protects against the effects of lightning impulses it is essential to use direct lightning protection devices (10/350 s waveform lightning impulse) and surge protection, induction (8/20 µs waveform lightning impulse).

  • PVT2 PHOTOVOLTAIC SURGE PROTECTION CLASS II

The PVT2 surge arresters offer many of the same benefits as the PVT1 series but are specifically designed to conform to the test parameters of the EN 50539-11 Type 1, Type 2 and UL® 1449 Edition 4 Type surge arresters 1 CASE. Because of its Class II/Type 2 classification, PVT2 is used in an inductive surge protection system that allows precise protective lightning protection designs to be realized while keeping project costs down.

Untitled 1                          kt pvt 2

Product Dimensions PVT1 and PVT2 – Measurement Unit: Inches / [mm]

Hướng dẫn chọn thiết bị cắt sét PVT

Symbolized product name: PVTXYYYR PVTX = Product name YYY = the maximum continuous operating voltage. 
Max Continuous Operating Voltage
(Ucpv/ Vpvdc)
R = Remote monitoring port

(Remote contact)

pvt 2  PVT1 = Dinrail Class I+II

PVT2 = Dinrail Class II

1000 = 1100V

1500 = 1500V

remote contact

For example

PVT11000R: PVT1 1000 R
 Explain Product's name Ucpv/ Vpvdc Remote monitoring gateway

Connection diagram

sddn pvt                                      sdnl pvt

         Connection diagram of PVT1 and PVT2                    Diagram principlesof PVT21000M (other models also follow this principle diagram)

PVT1 and PVT2 equipment line parameters 

PARAMETER PVT11000R PVT11500R PVT21000R PVT21500R
Maximum lightning current (8/20μs pulse pattern)
Max Discharge Current (Imax)
40kA 8/20μs 30kA 8/20μs
Lightning current (10/350μs pulse)
Impulse Current (Iimp)
6,25kA 10/350μs 5,00 kA 10/350 μs
Total lightning current
Total Discharge Current (Itotal)
12,5kA 10/350μs

50kA 8/20μs

10kA 10/350μs

40kA 8/20μs

50kA 8/20μs 40 kA 8/20 μs
Protection mode
Protection Modes
-ve    ̶   PE
-ve    ̶   +ve
+ve   ̶   PE
Module thay thế
Replacement Module
PVT1500M

PVT1500SM

PVT1750M

PVT1750SM

PVT2500M PVT2750M

Thông số áp dụng theo tiêu chuẩn EN 50539-11:2013+A1:2014

Max Continuous Operating Voltage
Điện áp làm việc lớn nhất (Ucpv)
1100Vdc 1500Vdc 1100Vdc 1500Vdc
Dòng tản sét danh định (dạng xung 8/20μs)
Nominal Discharge Current (In)
20kA 8/20μs
Điện áp bảo vệ
Voltage Protection Level (Up)
4000V 5000V 4000V 5000V
Khả năng chịu dòng ngắn mạch
Short Circuit Current Rating (Isccr)
11kA

Thông số áp dụng theo tiêu chuẩn UL® 1449 Edition 4

Max Continuous Operating Voltage
Điện áp làm việc lớn nhất (Vpvdc)
1100Vdc 1500Vdc 1100Vdc 1500Vdc
Dòng tản sét danh định (dạng xung 8/20μs)
Nominal Discharge Current (In)
20kA 8/20μs
Điện áp bảo vệ
Voltage Protection Level (VPR)
2500V 4000V 3000V 4000V
Khả năng chịu dòng ngắn mạch
Short Circuit Current Rating (SCCR)
50kA 65kA 50kA 65kA

For detailed product specifications, please refer to the catalog (here).

Structure of lightning arrester PVT1 and PVT2

ket cau pvt